Communication Between two E1000 HMI and mitsubishi Fx2n PLC

Connection
between 2 E-Terminals and FX2N PLC.
 The required material for the setup is
as follows

Sr.
no.
Material
1
PLC           :FX Series
2
CPU           :FX2N
3
HMI          : E1101 ,E1071
4
HMI S/W   
:E-Designer Ver: 7.31

  Two E-Terminals
are connected to FX-2N PLC using MISTU- CAB14A       

 and MISTU-CAB
6Aa

 
 The required cables are as follows

    

Sr. no.
Item
Description
1
MISTU-CAB 6Aa
Prog.Cable For
E-Terminal
And Comm. Cable
between E1071 and E-1101
2
MISTU-CAB 14A
Comm. Cable for
E-Terminal to FX2N PLC

 

E1101 Program Setting


STEP 1: Select Controller FX and FX Series Serial driver for Controller.

 Snapshot
of Controller 1 Setting in E1101

 Put Controller 1 in COM 1 (RS422) Port
in Peripheral Configuration as shown below.

 

E1071 Program Setting

STEP 1: Select FX-Series serial Controller in COM 2 (RS232) Port as                shown
below.