Communication Between two E1000 HMI and mitsubishi Fx2n PLC

Communication Between two E1000 HMI and Mitsubishi Fx2n PLC

Connection between 2 E-Terminals and FX2N PLC

 The required material for the setup is as follows
Sr.no.
Material
1
PLC           :FX Series
2
CPU           :FX2N
3
HMI          : E1101 ,E1071
4
HMI S/W    :E-Designer Ver: 7.31
  Two E-Terminals are connected to FX-2N PLC using MISTU- CAB14A   and MISTU-CAB 6Aa
 
Communication Between two E1000 HMI and Mitsubishi Fx2n PLC
Communication Between two E1000 HMI and Mitsubishi Fx2n PLC
 The required cables are as follows

 

Sr. no.
Item
Description
1
MISTU-CAB 6Aa
Prog.Cable For E-Terminal And Comm. Cable between E1071 and E-1101
2
MISTU-CAB 14A
Comm. Cable for E-Terminal to FX2N PLC
 
E1101 Program Setting
STEP 1: Select Controller FX and FX Series Serial driver for Controller.
 Snapshot of Controller 1 Setting in E1101
 Put Controller 1 in COM 1 (RS422) Port in Peripheral Configuration as shown below.

 

 
E1071 Program Setting
STEP 1: Select FX-Series serial Controller in COM 2 (RS232) Port as  shown below.