Judge the Error through the Indicator at the Front
Panel
Panel
When error occurred for the DVP PLC, please check:

POWER
LED
There is a “POWER” LED at the front of the MPU. When
the MPU is powered On, the green LED light will be on. If the indicator is not
on when the MPU is powered up and with the input power being normal, it is an
indication that the PLC is out of order. Please have this machine replaced or
have it repaired at a dealer near you.
the MPU is powered On, the green LED light will be on. If the indicator is not
on when the MPU is powered up and with the input power being normal, it is an
indication that the PLC is out of order. Please have this machine replaced or
have it repaired at a dealer near you.
RUN
LED
Identify the status of the PLC. When the PLC is in
operation, this light will be on, and users could thus useHPP or the ladder
diagram to edit program and give commands to make the PLC “RUN” or “STOP”.
operation, this light will be on, and users could thus useHPP or the ladder
diagram to edit program and give commands to make the PLC “RUN” or “STOP”.
ERROR
LED
1. If illegitimate program is input to the MPU, or
that the commands and devices of the program exceed the allowable range, the
indicator will thus be blinking. In this case, the user should inquire about
the errorcode from the special data register D1004 in the MPU and look it up in
the Error Code Table. After the error is found and the program is revised, send
the revised version to the MPU.
that the commands and devices of the program exceed the allowable range, the
indicator will thus be blinking. In this case, the user should inquire about
the errorcode from the special data register D1004 in the MPU and look it up in
the Error Code Table. After the error is found and the program is revised, send
the revised version to the MPU.
2. If the PLC is unable to perform function, and the
LED is blinking swiftly, it indicates that 24VDC power does not supply
sufficient power. Please check whether the power supply of 24VDC is normal or
not.
LED is blinking swiftly, it indicates that 24VDC power does not supply
sufficient power. Please check whether the power supply of 24VDC is normal or
not.
3. When the ERROR LED is on (not blinking), it is an
indication that the execution time of the program circuit has exceeded the
preset time-out limit (setting of D1000). To check the program circuit or use
theWDT command to improve the error status. Once program modification is
completed, user can re-download the program of PLC and the ERROR LED will be
off. If the ERROR LED is still keep on,please turn off the power and check if
there’s any noise or any conductive invader inside the PLC.“Input” LED The
On/Off signals of the input point could be displayed through the “Input” LED,
or monitor the status of the input point through the device HPP monitoring
function. Once the motion of the input point is valid, the LED is on.
Therefore, if errors are detected via using HPP, the LED and the input signal
circuits then are used to check whether the status is normal. Especially when
the electronic switch of great electric leakage is utilized, the input point is
usually witnessed with unexpected motions.
indication that the execution time of the program circuit has exceeded the
preset time-out limit (setting of D1000). To check the program circuit or use
theWDT command to improve the error status. Once program modification is
completed, user can re-download the program of PLC and the ERROR LED will be
off. If the ERROR LED is still keep on,please turn off the power and check if
there’s any noise or any conductive invader inside the PLC.“Input” LED The
On/Off signals of the input point could be displayed through the “Input” LED,
or monitor the status of the input point through the device HPP monitoring
function. Once the motion of the input point is valid, the LED is on.
Therefore, if errors are detected via using HPP, the LED and the input signal
circuits then are used to check whether the status is normal. Especially when
the electronic switch of great electric leakage is utilized, the input point is
usually witnessed with unexpected motions.
Output
LED
The “Output” LED is designed mainly for display the
On/Off status of the output signals. When the “Output” LED is On or Off and
that the loading is of an opposite motion, the following conditions should be
attended to:
On/Off status of the output signals. When the “Output” LED is On or Off and
that the loading is of an opposite motion, the following conditions should be
attended to:
1. The output contact might be melted down and
blocked up due to overload or load in short-circuit, defect
happened consequently under this situation.
blocked up due to overload or load in short-circuit, defect
happened consequently under this situation.
2. If the output contact is function as undesired,
be sure to check the output wiring circuit and whether the screw is tightened
or not.
be sure to check the output wiring circuit and whether the screw is tightened
or not.
PLC Error
Code Table

PLC Periodic Inspection
Since the DVP series PLC does not utilize
disposable components, there is thus no need to replace most of the components.
However, if the output relay turns on/off frequently, or drive the large load
current too often, life of the output contact will thus be decreased. Under a
condition like this, periodic inspection is then needed to ensure if the
contact is of the “Permanently Open” status or of the short-circuit status.
Moreover, the following precautions should be noted:
disposable components, there is thus no need to replace most of the components.
However, if the output relay turns on/off frequently, or drive the large load
current too often, life of the output contact will thus be decreased. Under a
condition like this, periodic inspection is then needed to ensure if the
contact is of the “Permanently Open” status or of the short-circuit status.
Moreover, the following precautions should be noted:
1. Do not mount the DVP under direct sunlight or
near any heat-radiation objects.
near any heat-radiation objects.
2. Do not install the DVP-PLC in places subject to
high temperature, high humidity, excessive vibration,corrosive gasses, liquids,
airborne dust and metallic particles.
high temperature, high humidity, excessive vibration,corrosive gasses, liquids,
airborne dust and metallic particles.
3. Check periodically whether the wiring and
terminals are tightened and conducted properly
terminals are tightened and conducted properly