Mitsubishi PLC FX2N & HMI E1000 Networking using BDTP Technology

Networking between E1000 terminals using BDTP Technology  

 1.   Material Requirement
The required material for the setup is as follows
Sr.
no.
Material
1
PLC Type  : FX Series
2
CPU:  FX2N PLC
3
PLC S/W  : GX Developer Ver. 8.45X
4
HMI  E1041,HMI E1043
5
Other
 2. Diagram
Network communication via BDTP is used to connect two or more E1000-series operator terminals to one or two controllers or several operator terminals to
two or more controllers, with retained performance.

Networking between E –Terminals using BDTP Technology
Networking between E –Terminals using BDTP Technology

Figure 1 Networking between E –Terminals
using BDTP Technology

 

 Cables
The required cables are as follows
    
Sr. no.
Item
Description
1
Medoc cable
Prog. cable for FX PLC
2
Ethernet Cross Cable
Comm. Cable for E-Terminal to E-Terminal & PLC*1
*1 To connect the E-Terminal to E-Terminal if HUB is used then Serial    Straight cable is used.
  
4.  E-Designer Program Setting
 Set IP 192.168.1.1 of BDTP Server in Peripheral Configuration as below.

 

Peripheral Configuration of BDTP Server
Peripheral Configuration of BDTP Server

Fig: Peripheral Configuration of BDTP Server

 Network Connection/Network services:
Select Network Services, Select BDTP Server to edit Max Client.

 

Fig. Network Connection of BDTP Server

 

Fig. Network services of BDTP Server
   5.  BDTP Client Setting
  
   Set IP 192.168.1.2 of BDTP Client as below

Fig: Peripheral Configuration of BDTP Client

  5.  BDTP Client Setting
For the network service BDTP Client, the IP Addresses for the BDTP Servers in the network from which the client is to collect information are defined. Select BDTP Client
in the list and click Edit to enter the settings.

 

Fig. Network services of BDTP Client

Youtube Link