PTO [Pulse Train Output] Instruction in Allen Bradley PLC

PTO [Pulse Train Output] Instruction in Allen Bradley PLC

For MicroLogix 1200 and MicroLogix 1500
Example of Instruction
PTO [Pulse Train Output] Instruction in Allen Bradley PLC
PTO [Pulse Train Output] Instruction in Allen Bradley PLC

 

Description 
Use this instruction to control and monitor the pulse train output function, which in turn controls the physical PTO output. The operation of the PTO function is controlled by a state machine. The rung state when the instruction
is executed is only one of several inputs used to control this state machine, the other being the state of the enable bit. The frequency that appears at the physical output only changes at a pulse boundary. This means that the ramp at
the physical output during the Acceleration and Deceleration phases are dependent on the processor scan time. For this reason we recommend operating the PTO from the STI user interrupt.

Operation

When executed on a true rung, the PTO instruction sets (1) the EN bit and executes the state machine.
When executed on a false rung, the PTO instruction resets (0) the EN bit and executes the state machine.
Pre-First Pass
·
The EN, CO, PO, NO, ER, ID, AS, RS, DS and DN Status/Control bits are reset.
·
The Error Code is set to zero.
·
The Current Frequency and Current Position are set to zero.
·
The state machine are initialized so that the Pre-Idle state is entered the first time a PTO instruction is executed.
MCR Zone Execution
In an active MCR zone, the PTO operates as if the rung state were false. 
Entering Parameters
Enter a 0 or a 1 for the PTO number. The PTO status and control information is contained in a Pulse Output (PO) control file or (PTO) function file. A list of equirements regarding the use of the PTO follows:
·
You can assign outputs O:0/2 and O:0/3 to any of the PTO or PWM functions but, the same output cannot be assigned to more than one function. 
·
The PTO number also designates which PTO control file is used by the instruction.
·
There is no restriction on the number of PTO instructions that can be in your program. Each time one of the instructions is executed, it updates the PTO function as described by the PTO state machine.
·The output image for the output controlled by the PTO function is updated to reflect the state of the physical output every time that the PTO instruction is evaluated.
·
If the PTO function is being used, the output image for the output controlled by the PTO function is not transferred to the physical output. This constraint also applies to immediate outputs. The PTO function is being used if
and only if a transition out of the Pre-Idle state is made. For example, a PTO instruction may be contained in a subroutine or interrupt file that is never executed, in this case the PTO function is not used.
·
Immediate outputs update the output image (but not the physical output.)
·
If the output controlled by the PTO function is forced, the force overrides the PTO and the PTO errors out. Some of the errors generate a recoverable major fault (code 003B). Click here for a list of faults which may be generated.
·
When the PTO is in the Idle or Error state, the output controlled by the PTO is always off (unless a force overrides the physical output.)
·
If the PTO instruction is being used when a power fail occurs, the corresponding output image are set to zero.
Note:A maximum of two elements can be configured for the PTO and PWM files combined.
Source:Rockwell Softwar Inc.